Live Detection of Cable Insulation Aging Defects in 35kV Switchgear
Download as PDF
DOI: 10.25236/icemit.2019.036
Author(s)
Jianli Zhao, Yujia Hou, Taowei Liu, Bo Liu
Corresponding Author
Jianli Zhao
Abstract
Through the live detection of partial discharge, it is found that there is an insulation discharge phenomenon at the end of the B phase cable of a 35kV Switchgear. After power failure inspection, it was found that there was obvious discharge traces in the contact position between B phase cable and ground whip. After the disintegration of the cable head, it is found that the production process of the cable head is bad and the shielding layer is missing, which leads to the uneven local electric field. Meantime, it is also found that there is an aging phenomenon in the main insulation of B phase cable, and its colour has been changed from white to dark yellow. The insulation defect is effectively discovered by the live inspection work, which makes the occurrence of power accidents be avoided with the equipment long-term operation.
Keywords
Switchgear, Partial discharge, Electrification detection, Power cable